Arte SheetsLearn. Try. Understand.

Hydronic HVAC Systems, DOAS + Active Chilled Beams & Sensible Cooling Engineering

Active Chilled Beam Induction Ratio & Cooling Formula

Calculate Induced Room Secondary Airflow Q_sec (L/s), Primary DOAS Ventilation Sensible Cooling (W), Secondary Hydronic Coil Sensible Cooling (W), and Total Chilled-Beam Sensible Capacity (W).

A tiny 28 L/s primary DOAS jet entrains 4x–5x room air across the chilled-beam coil—decoupling ventilation from zone sensible load

Conventional VAV all-air systems haul huge ducts of air just to move sensible watts; Dedicated Outdoor Air System (DOAS) + Active Chilled Beams supply only dehumidified Primary Ventilation Air Q_pri (L/s) through high-velocity Venturi nozzles inside the ceiling beam. By turbulent jet entrainment (Induction Ratio IR = Q_sec / Q_pri, typically 3.0 to 5.5 with zero room fan motor), Q_sec = IR * Q_pri (L/s) of warm room air at T_room (°C) is drawn upward across a dry 15–17 °C chilled-water finned coil (kept strictly above room dew point so condensate pans are eliminated), cooling to T_sec,out (°C) before mixing with T_pri (°C) and discharging across the ceiling via Coanda effect: Total Sensible Zone Cooling is Q_tot = 1.20 * 1.006 * Q_pri * (T_room - T_pri) + 1.20 * 1.006 * (IR * Q_pri) * (T_room - T_sec,out) watts.

Verify on a 2.4 m Laboratory Active Chilled Beam—Primary_DOAS_Airflow Q_pri = 28.0 L/s (B2), Nozzle_Induction_Ratio IR = 4.20 (B3 -> Induced Room Air Q_sec = 117.6 L/s in E2), Room_Design_Temp T_room = 24.5 °C (B4), Primary_Supply_Temp T_pri = 14.0 °C (B5 -> Primary Air Cooling = 354.9 W in E3), and Secondary_Leaving-Coil_Temp T_sec,out = 17.5 °C (B6 -> Hydronic Coil Cooling = 993.8 W in E4): Total Chilled-Beam Sensible Capacity hits 1,348.7 W (73.7% delivered hydronically with zero terminal fan power!, E5).

Active Chilled Beam KPI (Qpri=28 L/s @ 14°C, IR=4.2, Troom=24.5°C, Tcoil=17.5°C)FormulaVerified Output
Induced Secondary Airflow (L/s)Primary_Air_L_s * Induction_Ratio_IR117.6 L/s (154.0 L/s @ high-nozzle IR=5.5)
Primary DOAS Sensible Cooling (W)1.20 * 1.006 * Qpri_L_s * (Troom - Tpri)354.9 W
Hydronic Coil Sensible Cooling (W)1.20 * 1.006 * Qsec_L_s * (Troom - Tcoil)993.8 W (1,301.4 W @ IR = 5.5)
Total Beam Sensible Cooling (W)Primary_Cooling_W + Hydronic_Coil_W1,348.7 W (1,656.3 W @ IR = 5.5)

Nozzle Induction Entrainment & Dual-Stream Chilled-Beam Cooling Formula

Validate Primary_Air > 0 L/s, Induction_Ratio IR in [1.5, 8.0], T_pri < T_room, and T_sec,out in [12, T_room) °C (>= 14 °C chilled water prevents ceiling condensation Rain-Out unless DOAS holds space dew point below 12 °C).

=LET(qp_l, B2, ir_n, B3, tr_c, B4, tp_c, B5, ts_c, B6, qs_l, qp_l * ir_n, wp_w, 1.2 * 1.006 * qp_l * (tr_c - tp_c), ws_w, 1.2 * 1.006 * qs_l * (tr_c - ts_c), IF(OR(qp_l <= 0, ir_n < 1.5, ir_n > 8, tp_c >= tr_c, ts_c < 12, ts_c >= tr_c), "Invalid Chilled Beam Input", ROUND(wp_w + ws_w, 1)))

High-Induction Nozzle Plate Swap Check (Set Induction Ratio IR B3 = 5.50)

Select a higher-pressure small-orifice nozzle plate raising Induction Ratio B3 from 4.20 to 5.50 at the exact same 28.0 L/s DOAS ventilation rate: Induced Secondary Airflow E2 rises to 154.0 L/s, Hydronic Coil Output E4 climbs to 1,301.4 W, and Total Beam Cooling E5 reaches 1,656.3 W.

=IF(ISTEXT(E5), E5, ROUND(1.2 * 1.006 * (B2 * B3) * (B4 - B6), 1))

Try the example

Use the original values or change them to test your understanding.

Further reading