ASHRAE Huebscher Rectangular Equivalent Duct Diameter Formula

Calculate Huebscher Equal-Friction Circular Equivalent Diameter De (mm), Wetted-Perimeter Hydraulic Diameter Dh (mm), Rectangular Duct Air Velocity (m/s), and Velocity Pressure Pv (Pa).

Never size rectangular HVAC ducts on a round ductulator using hydraulic diameter Dh—equal Dh does NOT carry equal airflow

HVAC duct friction charts plot pressure loss per meter Delta_P / L against Volumetric Airflow Q for round spiral ducts of diameter D_round. When low ceiling plenums force a rectangular duct of width a (mm) and height b (mm), substituting Hydraulic Diameter D_h = 4*A / P = 2*a*b / (a + b) directly into the round friction chart under-predicts capacity because D_h preserves mean velocity rather than volumetric flow at equal friction. Richard Huebscher (ASHRAE Fundamentals) solved Darcy-Weisbach equal pressure drop per unit length AT EQUAL VOLUMETRIC AIRFLOW Q, yielding the universal Equal-Friction Circular Equivalent Diameter D_e = 1.30 * ((a * b)^0.625) / ((a + b)^0.25).

Test a 600 mm x 250 mm Supply Trunk Carrying 4,500 m³/h—Duct_Width a = 600.0 mm (B2), Duct_Height b = 250.0 mm (B3), Volumetric_Airflow Q = 4,500.0 m³/h (B4), and Air_Density rho = 1.20 kg/m³ (B5): Huebscher Equivalent Round Diameter D_e equals 413.66 mm (E2, vs 352.94 mm Hydraulic Diameter D_h in E3), Mean Trunk Velocity hits 8.33 m/s (E4), and Velocity Pressure P_v = 0.5 * rho * v^2 equals 41.67 Pa (E5).

ASHRAE Duct Sizing KPI (600x250 mm Trunk, Q=4,500 m³/h, rho=1.20 kg/m³)FormulaVerified Output
Huebscher Equivalent Diameter De (mm)1.30 * ((a * b)^0.625) / ((a + b)^0.25)413.66 mm (383.55 mm @ flat 1000x150)
Hydraulic Diameter Dh (mm)(2 * a * b) / (a + b)352.94 mm (260.87 mm @ flat 1000x150)
Mean Duct Air Velocity (m/s)(Q_m3_hr / 3600) / ((a/1000)*(b/1000))8.33 m/s (unchanged at equal 0.15 m²)
Duct Velocity Pressure Pv (Pa)0.5 * Air_Density * (Velocity_m_s ^ 2)41.67 Pa

ASHRAE Huebscher Equal-Friction Diameter & Dynamic Velocity Pressure Formula

Validate Duct_Width a > 0, Duct_Height b > 0 (ASHRAE recommends aspect ratio MAX(a,b)/MIN(a,b) <= 8 to avoid excessive corner friction and sheet-metal drumming), Airflow Q > 0, and Air_Density in [0.5, 2.0] kg/m³. When a mechanical consultant shares a duct riser schedule in Arte Sheets, a commissioning suggester can test tight soffit flattening scenarios in Suggest Mode without overwriting locked design static-pressure baselines.

=LET(da_m, B2, db_m, B3, qf_h, B4, rh_a, B5, IF(OR(da_m <= 0, db_m <= 0, (MAX(da_m, db_m) / MIN(da_m, db_m)) > 10, qf_h <= 0, rh_a < 0.5, rh_a > 2), "Invalid Duct Input", LET(va_s, (qf_h / 3600) / ((da_m / 1000) * (db_m / 1000)), ROUND(0.5 * rh_a * (va_s ^ 2), 2))))

High-Aspect-Ratio 1,000 x 150 mm Pancake Soffit Penalty Check (Same 0.15 m² Cross-Section)

Flatten the exact same 0.15 m² cross-sectional area into a 6.67:1 pancake duct (a B2 = 1,000.0 mm, b B3 = 150.0 mm): Air Velocity E4 stays 8.33 m/s, yet wetted-perimeter friction shrinks Huebscher Equivalent Round Diameter E2 from 413.66 mm down to 383.55 mm (D_h E3 drops to 260.87 mm)—proving high-aspect pancake ducts choke fan static pressure.

=IF(ISTEXT(E5), E5, ROUND((1.3 * ((B2 * B3) ^ 0.625)) / ((B2 + B3) ^ 0.25), 2))

Try the example

Use the original values or change them to test your understanding.