Centrifugal Fan Affinity Laws & VFD Cubic Power Formula
Calculate VFD Turndown Airflow Q2 (m³/h), Quadratic Static Pressure Delta_P2 (Pa), Cubic Shaft Power P2 (kW), and Annual Fan Energy Savings (kWh/yr).
Slowing an AHU supply fan to 80% speed via VFD cuts airflow 20%—but slashes shaft power by nearly 49%
Throttling an air-handling unit (AHU) or industrial baghouse fan with a discharge damper wastes electricity fighting artificial static drop. Under the three Turbomachinery Fan Affinity Laws on a fixed parabolic system curve (zero static-pressure reset), changing impeller speed from N1 to N2 (RPM) scales: (1) Volumetric Airflow linearly Q_2 = Q_1 * (N2 / N1), (2) Fan Total/Static Pressure quadratically Delta_P_2 = Delta_P_1 * (N2 / N1)^2, and (3) Impeller Shaft Power CUBICALLY P_2 = P_1 * (N2 / N1)^3. That cubic exponent (0.80^3 = 0.512) makes Variable Frequency Drive (VFD) retrofits the highest-ROI electrical efficiency upgrade in commercial HVAC and industrial dust collection.
Verify on a 24,000 m³/h Supply Fan VFD Retrofit—Rated_Airflow Q_1 = 24,000.0 m³/h (B2), Rated_Static_Pressure Delta_P_1 = 750.0 Pa (B3), Rated_Shaft_Power P_1 = 6.80 kW (B4), Nameplate_Speed N1 = 1,450 RPM (B5), VFD_Operating_Speed N2 = 1,160 RPM (80% speed, B6), and Annual_Run_Hours = 6,000 hr/yr (B7): VFD Airflow equals 19,200.0 m³/h (E2), Static Pressure drops to 480.00 Pa (E3), Shaft Power plunges to 3.48 kW (E4), saving 19,910.4 kWh/year (E5).
| Fan Affinity Law KPI (24,000 m³/h, 750 Pa, 6.80 kW @ 1,450 -> 1,160 RPM) | Formula | Verified Output |
|---|---|---|
| VFD Turndown Airflow Q2 (m³/h) | Q1 * (RPM2 / RPM1) | 19,200.0 m³/h (14,400.0 @ 870 RPM) |
| VFD Static Pressure dP2 (Pa) | dP1 * ((RPM2 / RPM1) ^ 2) | 480.00 Pa (270.00 Pa @ 870 RPM) |
| VFD Cubic Shaft Power P2 (kW) | P1 * ((RPM2 / RPM1) ^ 3) | 3.48 kW (1.47 kW @ 60% speed) |
| Annual Electricity Saved (kWh/yr) | (P1 - P1 * ((RPM2/RPM1)^3)) * Hours | 19,910.4 kWh (31,987.2 kWh @ 870 RPM) |
Linear-Quadratic-Cubic Fan Affinity Laws & Annual VFD kWh Savings Formula
Validate Q_1 > 0, Delta_P_1 > 0, P_1 > 0, RPM_1 > 0, RPM_2 in (0, 1.2 * RPM_1] (note: running above 100% synchronous speed rapidly overloads motor amps by (N2/N1)^3), and Annual_Hours in (0, 8,760].
=LET(qf_r, B2, dp_r, B3, pw_r, B4, nr_p, B5, nv_p, B6, hr_y, B7, IF(OR(qf_r <= 0, dp_r <= 0, pw_r <= 0, nr_p <= 0, nv_p <= 0, nv_p > 1.2 * nr_p, hr_y <= 0, hr_y > 8760), "Invalid Fan Law Input", LET(sr_t, nv_p / nr_p, ROUND((pw_r - (pw_r * (sr_t ^ 3))) * hr_y, 1))))Part-Load 60% Night/Off-Peak Setback Check (Set VFD Speed N2 = 870 RPM)
Step the VFD down to 60% speed (N2 B6 = 870 RPM): Airflow E2 scales linearly to 14,400.0 m³/h, Static Pressure E3 drops to 270.00 Pa (0.36x), Shaft Power E4 collapses by 78.4% down to 1.47 kW (0.216x), and Annual Energy Saved E5 jumps to 31,987.2 kWh/year.
=IF(ISTEXT(E5), E5, ROUND(B4 * ((B6 / B5) ^ 3), 2))Try the example
Use the original values or change them to test your understanding.