Arte SheetsLearn. Try. Understand.

Drinking-Water Disinfection, US EPA SWTR & Clearwell Hydraulics

Disinfection Contact Time and CT: A Clearwell Arithmetic Example

Calculate theoretical detention time, an illustrative baffling-adjusted contact time and CT, while distinguishing these values from regulatory disinfection credit.

Detention time, T10 and CT

For a constant-flow arithmetic example, theoretical detention time is volume divided by flow. Actual water residence times vary with the basin and hydraulic conditions. EPA guidance describes T10 as an estimate of the time that at least 90% of water passing through a treatment unit is retained; it may be established through a tracer study or estimated using a suitable, approved baffling factor.

CT combines a disinfectant residual C in mg/L and contact time T in minutes. A calculated CT by itself does not establish pathogen inactivation or compliance. The applicable disinfection credit depends on the disinfectant, microorganism, water temperature, pH where relevant, sampling and approved regulatory method.

Hypothetical exampleCalculationResult
1,500 m³ and 25 m³/minTheoretical detention = volume / flow60 min
Illustrative factor 0.50Estimated T10 = 60 × 0.5030 min
Residual 1.60 mg/LIllustrative CT = 1.60 × 3048 mg·min/L

Calculate theoretical detention time

Enter volume in m³ in B2 and flow in m³/min in B3. Put this formula in B6. It assumes the entered volume is available and flow is constant for the example.

=IF(COUNT(B2:B3)<>2,"Enter numeric volume and flow",IF(OR(B2<=0,B3<=0),"Check volume and flow",B2/B3))

Estimate contact time with an illustrative factor

Enter a factor in B4 and put this formula in B7. The example uses 0.50 only to demonstrate multiplication; it is not a measured T10 or a factor approved for a particular clearwell. EPA recommends coordination with the applicable regulator when selecting an estimated baffling factor.

=IF(ISNUMBER(B6),IF(COUNT(B4)<>1,"Enter numeric baffling factor",IF(OR(B4<=0,B4>1),"Check example baffling factor",B6*B4)),B6)

Calculate illustrative CT

Enter an appropriate residual in mg/L in B5. This formula multiplies it by B7. Actual compliance calculations require the correct sampling point, temperature, pH and the applicable approved pathogen-specific CT method; do not infer a Giardia log credit or permit status from this example.

=IF(ISNUMBER(B7),IF(COUNT(B5)<>1,"Enter numeric disinfectant residual",IF(B5<0,"Check residual",ROUND(B7*B5,2))),B7)

Try the example

Use the original values or change them to test your understanding.

Further reading