Architectural Illumination & Ergonomics, CIE 117 / EN 12464-1 Unified Glare Rating (UGR)

CIE Unified Glare Rating (UGR) Discomfort Formula

Calculate Single-Luminaire Guth Glare Term (L²*omega/p²), Cumulative Multi-Fixture Glare Sum, CIE 117 Unified Glare Rating UGR, and EN 12464-1 <=19 Office Compliance.

Paint an open-office ceiling matte black for "industrial aesthetics" while installing bare-diffuser LED panels and UGR jumps +9.5 points into painful visual glare

500 lux on a desk means nothing if high-angle 65° brightness stabs seated workers’ eyes. CIE Publication 117 & EN 12464-1 quantify psychological indoor discomfort glare on a logarithmic scale (10 imperceptible, 16 technical drawing limit, 19 standard office/classroom ceiling, 22 industrial assembly, 28 intolerable) via **Unified Glare Rating UGR = 8 * LOG10((0.25 / L_b) * SUM((L^2 * omega) / p^2)). For N representative visible luminaires of Projected Emitting Luminance L (cd/m²), Subtended Steradian Solid Angle omega (sr at observer eye), and Guth Off-Axis Position Index p (1.0 dead ahead to ~10 high overhead), glare grows with L^2 (6.0 UGR units per doubling of fixture brightness) AND inversely with Background Room Adaptation Luminance L_b = Eindirect / PI()** (cd/m²—dark walls/ceilings starve pupil adaptation and dramatically worsen glare).

Verify on a 12-Fixture Micro-Prismatic UGR < 19 Office Grid—Luminaire_Luminance L = 2,800 cd/m² (B2), Bright-Wall_Background L_b = 35.0 cd/m² (B3), Representative_Solid_Angle omega = 0.0018 sr (B4), Guth_Position_Index p = 2.40 (B5), and Visible_Luminaires N = 12 (B6): Single-Fixture Glare Term (L^2 * omega) / p^2 equals 2,450.0 (E2), 12-Fixture Sum equals 29,400.0 (E3), UGR equals 18.58 (<= 19) (E4), certifying "EN 12464-1 OFFICE PASS (<=19)" (E5).

CIE 117 UGR Glare KPI (omega=0.0018 sr, Guth p=2.40, N=12 Fixtures)FormulaVerified Output
Single-Fixture Glare Term(Luminaire_L_cd_m2 ^ 2 * Solid_Angle_sr) / (Guth_p ^ 2)2,450.0 (16,200.0 @ bare 7,200 cd/m²)
Multi-Fixture Glare SumVisible_Fixtures_N * Single_Fixture_Term29,400.0 (194,400.0 @ bare lens)
CIE 117 Unified Glare Rating8 * LOG10((0.25 / Background_Lb) * Glare_Sum)18.58 comfortable (28.08 PAINFUL GLARE)
EN 12464-1 Office Glare GateUGR <= 19.0 Reading / VDT Screen SpecEN 12464-1 OFFICE PASS (<=19)

CIE 117 Logarithmic Luminance-Contrast UGR & Guth Position Formula

Validate Luminaire_Luminance L in [200, 100,000] cd/m², Background L_b in [2, 500] cd/m², Solid_Angle omega in [0.0001, 0.1] sr, Guth_Position p in [1.0, 16.0], and Fixture_Count N in [1, 200] right on E2 (checking ISTEXT(E2) on E3..E4 so E5 text stays decoupled).

=LET(ll_c, B2, lb_c, B3, om_s, B4, gp_i, B5, nf_c, B6, st_g, ((ll_c ^ 2) * om_s) / (gp_i ^ 2), ug_r, 8 * LOG10((0.25 / lb_c) * nf_c * st_g), IF(OR(ll_c < 200, ll_c > 100000, lb_c < 2, lb_c > 500, om_s < 0.0001, om_s > 0.1, gp_i < 1, gp_i > 16, nf_c < 1, nf_c > 200), "Invalid UGR Input", IF(ug_r <= 19, "EN 12464-1 OFFICE PASS (<=19)", "EXCESSIVE DISCOMFORT GLARE (>19)")))

Bare Opal Diffuser (L = 7,200 cd/m²) Against Dark Exposed Ceiling (L_b = 15 cd/m²) Check

Substitute un-louvered opal flat panels (B2 = 7,200 cd/m²) beneath a dark charcoal exposed deck (B3 = 15.0 cd/m²): Single-Fixture Term E2 jumps 6.6x to 16,200.0 and UGR E4 rockets +9.50 points to 28.08—triggering "EXCESSIVE DISCOMFORT GLARE (>19)" (> 28 intolerable CIE ceiling) in E5.

=IF(ISTEXT(E2), E2, LET(st_g, ((B2 ^ 2) * B4) / (B5 ^ 2), ROUND(8 * LOG10((0.25 / B3) * B6 * st_g), 2)))

Try the example

Use the original values or change them to test your understanding.