Drilled & Grouted Micropile Bond & Structural Load Formula

Calculate Ultimate Grout-to-Ground Bond Capacity (kN), Allowable Geotechnical Bond Load (FS = 2.0, kN), Composite Casing+Grout Structural Capacity (kN), and Governing Load.

Small-diameter micropiles ignore end-bearing completely—and switch from geotechnical skin-friction failure in sand to structural steel yielding in bedrock

Low-headroom seismic retrofits and bridge underpins install Small-Diameter (150–300 mm) Drilled & Pressure-Grouted Micropiles (FHWA-NHI-05-039) using high-yield API N80 steel casing (F_y = 552 MPa, Steel Area A_s mm²) filled with neat cement grout (f’_c = 30–40 MPa, Core Area A_g mm²). Because a 200 mm tip has tiny area (0.031 m²), FHWA design neglects tip bearing (Qtip = 0) and evaluates TWO competing axial limit states: (1) Geotechnical Grout-to-Ground Side Bond along Uncased Bond Length L_b (m) of Diameter D_b (mm) at Nominal Bond Strength alphabond (kPa): **PG,ult = alphabond * PI() * (D_b / 1,000) * L_b (kN) and Allowable Bond PG,all = 0.50 * PG,ult (FS = 2.0), vs (2) FHWA ASD Plunging/Cased Structural Compression Pc,all = (0.47 * F_y * A_s + 0.40 * f’_c * A_g) / 1,000 (kN), with MIN(PG,all, Pc,all)** governing.

Verify on a Type B Pressure-Grouted Dense-Sand Micropile—Bond-Zone_Diameter D_b = 200 mm (B2), Bond_Length L_b = 9.0 m (B3), Pressure-Grouted_Sand_Bond alphabond = 320 kPa (B4), API_N80_Casing_+_Bar_Steel A_s = 3,420 mm² (B5) at F_y = 552 MPa (B6), and Internal_Grout_Area A_g = 24,800 mm² (B7) at f’_c = 35 MPa (B8): Ultimate Bond reaches 1,809.6 kN (E2), Allowable Geotechnical Bond equals 904.8 kN (E3) vs Structural Capacity 1,234.5 kN (E4)—so Geotechnical Bond governs at 904.8 kN (E5).

FHWA Micropile Limit-State KPI (Db=200 mm, Lb=9.0 m, N80 Steel, alpha=320 vs 680 kPa)FormulaVerified Output
Ultimate Grout-Ground Bond (kN)alpha_kPa * PI() * (Db_mm / 1000) * Lb_m1,809.6 kN (3,845.3 kN in granite)
Allowable Geotech Bond PG_all (kN)0.50 * Ultimate_Bond_kN (FS=2.0)904.8 kN (1,922.7 kN in granite)
Allowable Structural Pc_all (kN)(0.47 * Fy * As + 0.40 * fc * Ag) / 10001,234.5 kN
Governing Micropile Capacity (kN)MIN(Allowable_Bond, Allowable_Structural)904.8 kN (switches to 1,234.5 kN in rock)

FHWA Dual-Envelope Geotechnical Bond vs Composite Casing Compression Formula

Validate Bond_Diam D_b in [100, 400] mm, Bond_Length L_b > 1.0 m, Bond_Stress alpha > 30 kPa, Steel_Area A_s > 200 mm², Steel_Yield F_y in [250, 700] MPa, Grout_Area A_g > 2,000 mm², and Grout f’_c in [20, 60] MPa.

=LET(db_m, B2 / 1000, lb_m, B3, ab_k, B4, as_m, B5, fy_m, B6, ag_m, B7, fc_m, B8, pg_a, 0.5 * ab_k * PI() * db_m * lb_m, pc_a, (0.47 * fy_m * as_m + 0.4 * fc_m * ag_m) / 1000, IF(OR(B2 < 100, B2 > 400, lb_m <= 1, ab_k <= 30, as_m <= 200, fy_m < 250, fy_m > 700, ag_m <= 2000, fc_m < 20, fc_m > 60), "Invalid Micropile Input", ROUND(MIN(pg_a, pc_a), 1)))

Sound Granite Rock Socket (alpha = 680 kPa) Structural Casing Ceiling Switch Check (Set Bond B4 = 680 kPa)

Socket the identical 9.0 m bond zone into sound granite (alphabond B4 = 680 kPa): Allowable Geotech Bond E3 surges to 1,922.7 kN, so MIN(...) in E5 caps Governing Capacity cleanly at 1,234.5 kN—proving further rock drilling is wasted money unless casing wall thickness or center-bar steel area A_s is increased.

=IF(ISTEXT(E5), E5, ROUND((0.47 * B6 * B5 + 0.4 * B8 * B7) / 1000, 1))

Try the example

Use the original values or change them to test your understanding.