ASHRAE 90.1 Building Controls, Airside Economizers, Mixed-Air Dampers & Free Cooling
HVAC Airside Economizer Mixed-Air & Free-Cooling Formula
Calculate Modulating Outside-Air Damper Fraction (%), Mixed-Air Plenum Temperature T_mix (°C), Minimum-Ventilation Baseline Mixed Temp (°C), and Chiller Sensible Free-Cooling Saved (kW).
Running a chiller in 11 °C shoulder weather wastes 70+ kW when modulating AHU economizer dampers hit 14.5 °C supply air for free
Commercial internal-load buildings (data rooms, offices, retail) still demand 13–15 °C cold supply air even when outdoor dry-bulb T_oa sits comfortably at 5–16 °C. Under ASHRAE 90.1 Airside Economizer control, whenever T_oa < T_lockout (high-limit dry-bulb/enthalpy changeover, e.g. 19.0 °C), the AHU modulates opposing Outside-Air (OA) and Return-Air (RA) dampers above ASHRAE 62.1 Minimum Ventilation f_min (~15%–25%) to hit Mixed-Air Setpoint T_set: solving steady-mass energy balance f_oa * T_oa + (1 - f_oa) * T_ra = T_mix yields Modulated Outside-Air Fraction f_oa = MIN(1, MAX(f_min, (T_ra - T_set) / (T_ra - T_oa))) (reverting immediately to f_min whenever T_oa >= T_lockout so hot outdoor air is locked out). Compared against Minimum-Ventilation Baseline T_mix,min = f_min * T_oa + (1 - f_min) * T_ra, Sensible Chilled-Water Load Unloaded is Q_free = rho_air * c_p * V_dot * MAX(0, T_mix,min - T_mix) (1.20 * 1.006 * Q_m3_s * Delta_T) kW.
Verify on an 8.50 m³/s (18,000 CFM) Office Air-Handling Unit—Supply_Airflow V_dot = 8.50 m³/s (B2), Return_Air_Temp T_ra = 24.0 °C (B3), Cool_Autumn_Outside_Air T_oa = 11.0 °C (B4), Mixed-Air_Discharge_Setpoint T_set = 14.5 °C (B5), Minimum_Code_OA_Fraction f_min = 0.20 (20%, B6), and Economizer_High-Limit_Lockout T_lock = 19.0 °C (B7): Outside-Air Damper modulates to 73.08% OA (E2), Mixed-Air Temp hits 14.50 °C with ZERO mechanical cooling (E3, vs 21.40 °C at minimum 20% OA in E4), unloading 70.80 kW of sensible chiller load (E5).
| ASHRAE 90.1 Economizer KPI (8.5 m³/s, Tra=24 °C, Toa=11 °C -> Tset=14.5 °C, fmin=20%) | Formula | Verified Output |
|---|---|---|
| Modulated Outside-Air Damper (%) | IF(Toa>=Tlock, fmin, CLAMP((Tra-Tset)/(Tra-Toa)))*100 | 73.08% OA (20.00% min @ 22 °C lockout) |
| Actual Mixed-Air Temp T_mix (°C) | f_oa * Toa + (1 - f_oa) * Tra | 14.50 °C (23.60 °C @ 22 °C lockout) |
| Min-OA Baseline Temp T_base (°C) | f_min * Toa + (1 - f_min) * Tra | 21.40 °C (23.60 °C @ 22 °C lockout) |
| Sensible Free-Cooling Saved (kW) | 1.20 * 1.006 * Q_m3_s * MAX(0, Tbase - Tmix) | 70.80 kW (0.00 kW @ 22 °C lockout) |
ASHRAE 90.1 Modulating Economizer Damper & High-Limit Lockout Formula
Validate Airflow > 0 m³/s, T_set < T_ra, f_min in [0, 1], and T_lock <= T_ra.
=LET(qf_s, B2, tr_c, B3, to_c, B4, ts_c, B5, fm_n, B6, tl_k, B7, IF(OR(qf_s <= 0, ts_c >= tr_c, fm_n < 0, fm_n > 1, tl_k > tr_c), "Invalid Economizer Input", LET(fo_a, IF(to_c >= tl_k, fm_n, MIN(1, MAX(fm_n, (tr_c - ts_c) / (tr_c - to_c)))), tm_x, fo_a * to_c + (1 - fo_a) * tr_c, tb_s, fm_n * to_c + (1 - fm_n) * tr_c, ROUND(1.2 * 1.006 * qf_s * MAX(0, tb_s - tm_x), 2))))Warm 22.0 °C Summer Afternoon High-Limit Lockout Check (Set Outside Air Toa B4 = 22.0 °C)
Warm outdoor weather to B4 = 22.0 °C (>= 19.0 °C lockout): Economizer High-Limit Lockout snaps Outside-Air Damper E2 back to minimum 20.00% code ventilation, Mixed-Air Temp E3 matches Baseline 23.60 °C (E4), and Free-Cooling Savings E5 drop cleanly to 0.00 kW as the chilled-water coil takes over.
=IF(ISTEXT(E5), E5, ROUND(IF(B4 >= B7, B6, MIN(1, MAX(B6, (B3 - B5) / (B3 - B4)))) * 100, 2))Try the example
Use the original values or change them to test your understanding.