Lithium-Battery Dry-Room HVAC, Silica-Gel Desiccant Wheels & Psychrometric Mass Balance
Rotary Desiccant Wheel Moisture Removal & Regen Formula
Calculate AHRI 940 Moisture Removal Capacity MRC (kg/h), Process Latent Heat of Sorption Released (kW), Reactivation Heater Thermal Input (kW), and Specific Regeneration Energy (kWh/kg).
Cooling coils freeze solid near 0 °C dew point—sub-zero dry rooms rely on desiccant wheels that trade latent vapor into sensible heat
Chilled-water or DX cooling coils cannot dehumidify air below ~4 °C dew point (~5.0 g/kg) without icing the fins; pharmaceutical tablet rooms, ice rinks, and EV lithium-battery dry rooms use a slowly rotating (8–12 rev/h) honeycomb Silica-Gel / Molecular-Sieve Desiccant Wheel. Across the 270° Process Sector (Q_proc m³/h at dry-air density rho), water vapor adsorbs from Inlet Humidity Ratio w_in (g/kg) down to w_out (g/kg), delivering **Moisture Removal Capacity MRC = (Q_proc * rho * (w_in - w_out)) / 1,000** (kg/h) while releasing Latent Heat of Condensation + Wetting (~2,450 kJ/kg -> Q_lat = (MRC * 2,450) / 3,600 kW) as warm dry process air. Across the 90° Reactivation Sector (Q_reg m³/h heated through Delta_T_reg = 90–140 °C), Regeneration Thermal Power Q_reg,kW = ((Q_reg * rho) / 3,600) * 1.006 * Delta_T_reg desorbs the trapped moisture at Specific Thermal Intensity Q_reg,kW / MRC (kWh/kg water removed).
Verify on a Pharmaceutical Tablet-Press Desiccant Dehumidifier—Process_Airflow Q_p = 3,200.0 m³/h (B2), Air_Density rho = 1.20 kg/m³ (B3), Process_Inlet_Humidity w_in = 13.80 g/kg (B4), Dry_Discharge_Humidity w_out = 4.20 g/kg (1.4 °C dew point, B5 -> MRC = 36.86 kg/h in E2 & Latent Release = 25.09 kW in E3), Reactivation_Airflow Q_r = 1,050.0 m³/h (B6), and Reactivation_Heater_Rise Delta_T_r = 95.0 °C (B7): Reactivation Heater Input equals 33.45 kW (E4), or 0.91 kWh per kg of moisture removed (E5).
| AHRI 940 Desiccant Wheel KPI (Qp=3,200 m³/h, 13.8 -> 4.2 g/kg, Qr=1,050 m³/h @ +95°C) | Formula | Verified Output |
|---|---|---|
| Moisture Removal Capacity MRC (kg/h) | (Qproc * rho * (w_in_g_kg - w_out)) / 1000 | 36.86 kg/h (47.23 kg/h @ 1.5 g/kg deep dry) |
| Latent Sorption Heat Released (kW) | (MRC_kg_hr * 2450) / 3600 | 25.09 kW (32.14 kW @ 1.5 g/kg) |
| Reactivation Heater Power (kW) | ((Qreg * rho) / 3600) * 1.006 * dT_reg_C | 33.45 kW (44.01 kW @ +125 °C regen) |
| Specific Regen Energy (kWh / kg) | Reactivation_Power_kW / MRC_kg_hr | 0.91 kWh/kg (0.93 kWh/kg @ +125 °C) |
AHRI 940 Desiccant Moisture Removal Capacity & Specific Regeneration Formula
Validate Process_Air > 0 m³/h, Density in [0.8, 1.5] kg/m³, 0 <= w_out < w_in <= 40 g/kg, Regen_Air > 0 m³/h, and Regen_DeltaT in [40, 180] °C.
=LET(qp_h, B2, rh_a, B3, wi_g, B4, wo_g, B5, qr_h, B6, dt_r, B7, mr_k, (qp_h * rh_a * (wi_g - wo_g)) / 1000, pw_r, ((qr_h * rh_a) / 3600) * 1.006 * dt_r, IF(OR(qp_h <= 0, rh_a < 0.8, rh_a > 1.5, wo_g < 0, wi_g <= wo_g, wi_g > 40, qr_h <= 0, dt_r < 40, dt_r > 180), "Invalid Desiccant Input", ROUND(pw_r / mr_k, 2)))Sub-Zero Dew-Point 1.50 g/kg Deep-Drying Upgrade Check (Set w_out = 1.50 g/kg & Regen Rise = 125.0 °C)
Boost reactivation burner rise to B7 = 125.0 °C to drive Process Discharge Humidity down to B5 = 1.50 g/kg (-11 °C frost point): MRC E2 climbs to 47.23 kg/h (32.14 kW sorption heat in E3), Reactivation Power E4 rises to 44.01 kW, and Specific Regeneration Intensity E5 edges from 0.91 to 0.93 kWh/kg.
=IF(ISTEXT(E5), E5, ROUND(((B6 * B3) / 3600) * 1.006 * B7, 2))Try the example
Use the original values or change them to test your understanding.