Rupture Disk: Manufacturing Range and Burst Tolerance

Distinguish a manufacturing design range from a tolerance around a marked burst pressure using a manufacturer’s illustrative example.

Two different pressure ranges

A manufacturing design range is an agreed range within which a lot’s marked burst pressure may fall. Burst tolerance describes an allowed deviation around the marked pressure at a specified disk temperature. They are different concepts: a tolerance around one marked value does not have to lie inside the manufacturing design range.

For one product example, BS&B describes a desired pressure of 80 psig with a manufacturing range of −5 psi to +9 psi: the marked pressure is therefore between 75 and 89 psig. If an actual lot is marked 78 psig and the applicable burst tolerance is ±5%, arithmetic gives 74.10 to 81.90 psig around that mark. These values illustrate the terminology in that product example, not a universal tolerance or a device selection.

Illustrative quantityArithmeticResult
Manufacturing range for marked pressure80 − 5 to 80 + 9 psig75 to 89 psig
Tolerance interval around 78 psig mark78 × (1 − 0.05) to 78 × (1 + 0.05)74.10 to 81.90 psig

Calculate the illustrative intervals

Enter the desired pressure, the lower and upper manufacturing allowances in psi, a marked pressure in that range, and an illustrative symmetric tolerance as a percentage. The sheet computes the two arithmetic intervals. Product specifications can use different ranges, tolerances or conventions; use the actual manufacturer data and governing requirements.

=IF(COUNT(B2:B6)<>5,"Enter all numeric inputs",IF(OR(B2<=0,B3<0,B3>B2,B4<0,B5<B2-B3,B5>B2+B4,B6<0,B6>=100),"Check example inputs",ROUND(B5*(1+B6/100),2)))

Do not use the arithmetic as an acceptance decision

A marked burst pressure is associated with a specified disk temperature; a single assumed temperature multiplier does not establish behavior at other conditions. Disc material, type, medium, operating conditions, manufacturing range and burst tolerance need to be assessed for the actual device.

A rupture disk installed with a relief valve also affects the system’s capacity and pressure losses. An assumed combination factor or a simple comparison with vessel pressure does not establish code compliance or safe relief. Qualified personnel should use applicable current standards, manufacturer documentation, certified combination data and the project’s complete relief-system design.